PROFIBUS Redundancy Link Module RLM01

Compare
Categories: , Tag:
Availability

Unavailable

Description

Field devices equipped with only a single PROFIBUS DP interface can be integrated in the redundant PROFIBUS network by using the Redundancy Link Module RLM01.
Acting like an active switch, it converts two redundant lines to one PROFIBUS DP line or vice versa. The RLM01amplifies signal form and amplitude of the incoming data and monitors activities and error statuses of all three lines. Field devices equipped with only a single PROFIBUS DP interface, can be integrated in the redundant PROFIBUS network by using the Redundancy Link Module RLM01. Acting like an active switch, it converts two redundant lines to one PROFIBUS DP line or vice versa. The RLM01amplifies signal form and amplitude of the incoming data and monitors activities and error statuses of all three lines.

RLM01 at a glance:

Three PROFIBUS ports
Transparent for PROFIBUS configuration, i.e. no slave address required
Supports transmission rates of 9.6 Kbps to 12 Mbps
Serve up to 31 Profibus clients. While using repeaters (optical – electrical), this number can extend
Errors are signalized via an LED on the frontplate and a signaling contact
Specific messages that can be read at the 8-pin terminal strip serve diagnostic purposes
CE, UL and CSA certified
Type Approval Certificate “Germanischer Lloyd” for use in marine area. Conversion of one simple, non redundant PROFIBUS line into two reciprocally redundant lines A/B and vice versa.

Use on PROFIBUS DP/FMS lines
Automatic line selection
Transmission rate 9.6 kBit/s …. 12 MBit/s
Communication Monitoring
Repeater functionality
Wire cross section 8-pin terminal strip, up to 1.5 mm²
Redundant power supply, 24 VDC (+20 .. +33 V), 150 mA typically at 24 V
Operating temperature 0 … 50°C
Status and error display
Power supply monitoring
Potential-free signaling contact
Easy assembly on a DIN mounting rail

Documentation

Datasheet